TITLE:
Research on the Arrangement of Dew Point Temperature Detectors of Capillary Plane Radiation Air-Conditioning
AUTHORS:
Xuelai Liu, Jie Wu
KEYWORDS:
Capillary Plane Radiation Air-Conditioning; Dew Point Temperature Detectors; Arrangement
JOURNAL NAME:
Journal of Power and Energy Engineering,
Vol.2 No.4,
April
15,
2014
ABSTRACT: Based on analysis of the reason and process of condensation on ceiling radiant cooling panels, two kinds of arrangement of detectors are put forward. The physical model is established, the results show that detectors are arranged as the form of triangle is more suitable. It can not only satisfy the use requirement but also it is economical and practical. Finally we can conclude that the inlet water temperature 0.5°C higher than dew point temperature is safe and reliable.