TITLE:
Design of a Fixed-Order Robust Controller to Damp Inter-Area Oscillations in Power Systems
AUTHORS:
Abdlmnam Abdlrahem, Parimal Saraf, Karthikeyan Balasubramaniam, Ramtain Hadidi, Alireza Karimi, Elham Makram
KEYWORDS:
H∞, Multi-Machine Power System, Nyquist Diagram, Robust Control, Wind Penetrations, SVC
JOURNAL NAME:
Journal of Power and Energy Engineering,
Vol.4 No.3,
March
31,
2016
ABSTRACT: This paper presents the design of a robust fixed-order H∞ controller to damp out the inter-area oscillations and to enhance the stability of the power system. The proposed H∞ approach is based on shaping the open-loop transfer function in the Nyquist diagram through minimizing the quadratic error between the actual and the desired open loop transfer functions in the frequency domain under linear constraints that guarantee robustness and stability. The proposed approach is robust with respect to multi-model uncertainty closed-loop sensitivity functions in the Nyquist diagram through the constraints on their infinity norm. The H∞ constraints are linearized with the help of a desired open-loop transfer function. The controller is designed using the convex optimization techniques in which the difference between the open-loop transfer function and the desired one is minimized. The two-area four-machine test system is selected to evaluate the performance of the designed controller under different load conditions as well as different levels of wind penetrations.