The Resuming Insulation Discharge Failure and Conductor Overheating Failure Judgment Method of SF6 Electrical Equipment

HTML  Download Download as PDF (Size: 187KB)  PP. 122-127  
DOI: 10.4236/epe.2009.12019    5,641 Downloads   8,959 Views  Citations

Affiliation(s)

.

ABSTRACT

Through the long time track examination and disintegration to SF6 circuit breaker, we obtain the massive monitor data and massive pictures. The criteria of resuming insulation discharge failure conforming to CSO2/CH2S>7, is quite broad to SO2 and the H2S concentration permission. Even if it reaches 100µL/L, it will not be in danger immediately to the safe operation of equipment. We may plan, arrange, and overhaul calmly. When obtaining the bare conductor overheating failure, it has not involved the resuming insulation. We may use the resuming insulation discharge failure criterion.

Share and Cite:

X. ZHUANG, Z. LI and C. HUANG, "The Resuming Insulation Discharge Failure and Conductor Overheating Failure Judgment Method of SF6 Electrical Equipment," Energy and Power Engineering, Vol. 1 No. 2, 2009, pp. 122-127. doi: 10.4236/epe.2009.12019.