Busbar Differential Relaying Method Based on Combined Amplitude and Phase Information of High Frequency Transient Currents

HTML  Download Download as PDF (Size: 304KB)  PP. 1288-1292  
DOI: 10.4236/epe.2013.54B244    4,485 Downloads   5,649 Views  Citations

ABSTRACT

Busbar differential relaying method based on combined amplitude and phase information of high frequency transient currents is put forward in this paper for the speed and reliability problems of busbar protection based on fundamental frequency. Under the analysis of features of bus high frequency differential currents, complex wavelet analysis is used to extract the amplitude and phase features of 1/4 period high frequency differential currents, and amplitude and phase information are used to form the polar coordinates. Bus fault is identified intuitively and precisely according to polar locus differences. This polar coordinates represented busbar differential protection scheme based on high frequency transient signals can not only avoid TA saturation, realizing quick protection, lots of PSCAD/EMTDC simulations also show that this busbar differential protection scheme works well under different fault conditions.

Share and Cite:

X. Wu, Z. He and X. Li, "Busbar Differential Relaying Method Based on Combined Amplitude and Phase Information of High Frequency Transient Currents," Energy and Power Engineering, Vol. 5 No. 4B, 2013, pp. 1288-1292. doi: 10.4236/epe.2013.54B244.

Copyright © 2024 by authors and Scientific Research Publishing Inc.

Creative Commons License

This work and the related PDF file are licensed under a Creative Commons Attribution 4.0 International License.