Active-Disturbance-Rejection-Control for Temperature Control of the HVAC System

HTML  XML Download Download as PDF (Size: 1119KB)  PP. 1-9  
DOI: 10.4236/ica.2018.91001    1,491 Downloads   3,156 Views  Citations

ABSTRACT

Heating, ventilation, and air conditioning (HVAC) system is significant to the energy efficiency in buildings. In this paper, temperature control of HVAC system is studied in winter operation season. The physical model of the zone, the fan, the heating coil and sensor are built. HVAC is a non-linear, strong disturbance and coupling system. Linear active-rejection-disturbance-control is an appreciate control algorithm which can adapt to less information, strong-disturbance influence, and has relative-fixed structure and simple tuning process of the controller parameters. Active-rejection-disturbance-control of the HVAC system is proposed. Simulation in Matlab/Simulink was done. Simulation results show that linear active-rejection-disturbance-control was prior to PID and integral-fuzzy controllers in rising time, overshoot and response time of step disturbance. The study can provide fundamental basis for the control of the air-condition system with strong-disturbance and high-precision needed.

Share and Cite:

Huang, C. , Li, C. and Ma, X. (2018) Active-Disturbance-Rejection-Control for Temperature Control of the HVAC System. Intelligent Control and Automation, 9, 1-9. doi: 10.4236/ica.2018.91001.

Copyright © 2024 by authors and Scientific Research Publishing Inc.

Creative Commons License

This work and the related PDF file are licensed under a Creative Commons Attribution 4.0 International License.